Eurotherm
Bel mij terug! Invensys Operations Management
.

Universal Temperature/Pressure/Process Indicator - V408

Shop Online

The V408 is an 1/8 DIN, universal, 5 digit indicator with four alarms, two digital inputs and one SPDT relay output. Available with a green or red display, it accepts temperature inputs from J, K, T, L, N, R, S, B, C and Platinel II type thermocouples and three-wire Platinum 100 Ohm (Pt100) RTDs. Process variables such as 4-20mA, 1-5V and 0- 10V as well as strain gauge bridge inputs can also be measured.

Other thermocouple types or high accuracy 20 to 80 point custom  linearization curves can be configured at the factory. Square root extraction or eight-point curve linearization can be user defined in the field. A second process input is available to accept remote setpoints and compare signals such as the average or difference, or selecting minimum or maximum readings.

Four programmable setpoint alarms can be field configured as rate of change, deviation high or low, non-latching and high or low or new, latching . The new alarm indicates the situation when a latched alarm has not been acknowledged and the measured value crosses the setpoint trip level a second time. The deviation alarm enables the user to reference alarm setpoints relative to a remote (main) setpoint from a controller. This remote setpoint would be a DC signal input to the optional 2nd process input module. Alarm hysterisis (deadband) can be configured from 1 to 9999 process variable units. Each alarm has a programmable delay up to 999.9 seconds.

The alarms can be linked to either the one standard relay output or up to three optional relay or digital output modules. These alarms can be configured in combination (e.g., one or all four alarms linked to one or all relays) and they will operate in fail-safe (i.e., normally energized) or non-fail-safe modes. Additionally, the display can be configured for password protection, limiting access to any or all functions. An alarm blocking function is also configurable to prevent alarm tripping during process start-up.

Two digital input channels are provided to accept alarm acknowledgment (e.g., remote pushbutton). These two digital inputs or the optional triple-digital input modules can also be used for remote setpoint select, alarm acknowledge, process input select, bridge zero and span calibration and tare. Other functions include indicator control such as selecting full menu access, disabling the keypad lockout or simulating keypad functions.

The V408 indicator housing maintains a NEMA 4 (IP54) front panel seal and can be removed or unplugged from the front, without disconnecting any wiring. By disengaging the front panel clips the entire indicator and electronics can be quickly pulled from the panel.

Thermocouples, three-wire RTDs, bridge, voltage and mV signals can be accepted directly into the indicator. Current signals such as 4-20mA are input using the 2.49 Ohm shunt resistor included with the indicator and mounting hardware.

V408

FEATURES:

  • Universal Field Configurable Input for Thermocouple, RTD, mV, bridge, 0-10V and 4-20mA Signals

  • Optimal modular Design Provides 3 Option Slots plus one Optional Modbus® Communication Slot

  • Option modules for 2nd Input, DC Retrans, Sensor Excitation, 3 Digital Inputs and Outputs, and Relays

  • Four Field Configurable Setpoints Support Combination Alarm Functions, Rate of Change, Deviation Alarms, Alarm Blocking and Latching/Non-latching

  • IP54 Front Panel with Plug-in From Front Design for Quick Replacement (Low MTTR)

  • Wide Ranging Power Supply: 85 to 264VAC or optional 20 to 29V DC or AC

  • Three Year Warranty

The five-digit display (99999) is available in green or red and can be field configured to match the input signal range to the preferred engineering units. Offsets and two point slope adjustments are fully programmable to compensate for sensor variances.

Application

The V408 is an excellent solution for temperature, pressure, level, flow and other process variable measurements. The modular design was developed to allow it to be optimally configured for most indication, alarm and data acquisition applications.

The wide variety of option modules and programming functions make the V408 a valuable plant-wide indication solution. For example, the secondary input enables functions such as differential measurement and summing with the use of K values for signal scaling. This function is useful in monitoring the mixing of products or raw materials. The deviation alarm can be used to ensure that a product is not diluted or spoiled by significant process excursions beyond the setpoint.

The field configurable V408 is an ideal standardized solution for a variety of temperature measurement and on-off control applications. For example, it can be used to control the heating and cooling elements in an oven or environmental control system using two setpoints for the high and low temperature limits. Similarly, a 4-20mA or bridge pressure signal can be monitored and the setpoints can be used to control or alarm the gas pressure or liquid levels in a tank. Weight, flow, pressure, temperature, speed, position and rate are just some of the process variables that can be accurately displayed and monitored with this flexible and effective indicator.

Specifications

Display:

5 digit (-9999 to 99999), 3 programmable

decimal positions, red or green,

15.9mm (0.6 In.) high characters

Inputs/Outputs:

 

Analog Process Value (including second input)

  • Low Level Range: -100 to 100mV

  • High Level Range: 0-20mA, 0-10V

  • Sample Rate: 9Hz

 

Resolution:

<2mV for low levels, <2mV for high levels

 

Linearity:

Better than 0.2°C

 

Calibration Accuracy:

+0.2% of reading, or + 1°C or + 1LSD,

whichever is greater

 

User Calibration:

Low and high offsets can be applied

 

Input Filtering:

Off to 999.9 seconds

 

Thermocouples:

Types J, K, T, L, N, R, S, B and Platinel II

 

Cold Junction:

In automatic mode, >30 to 1 rejection of

ambient temperature change or external 0°C, 45°C, 50°C external references

3-wire Pt100: 0.3mA excitation current

Functions, 2nd analog input:

2nd process value, remote setpoint,

select min, select max., derived value

 

Digital Inputs: (contact closure or open collector)

 

Digital Inputs 1 and 2:

switching voltage/current (non-isolated

from the PV) 24VDC/20mA nominal

  • Off state Resistance: <100 Ohms

  • On State Resistance: >28K Ohms

 

Triple Contact Inputs:

Specification is as per digital inputs 1 & 2,

except inputs are functionally isolated

 

Externally powered (triple logic inputs):

  • Off State: <5V DC

  • On State: 10.8 to 30V DC @ 2.5mA

 

Functions:

Triple logic or contact inputs can be

configured for disable, alarm

acknowledge, keylock, remote

setpoint select, PV input 2 select,

and strain gauge 1&2 tare correction.

 

 

 

 

DC Retransmission:

  • Range: Scaleable between 0-20mA and 0- 10VDC

  • Resolution: 1 part in 10,000

  • Retransmission values: Process value, setpoint or setpoint error

 

Transmitter supply:

Rating: 20mA, 24V DC

 

Strain gauge bridge supply:

Bridge voltage: Software selectable, 5V or 10V DC

Bridge resistance: 300 Ohms to 10K Ohms

 

Alarms:

  • Number: Four alarms

  • Alarm types: High, low, deviation high, deviation low, deviation band, rate of change (seconds or minutes), new alarm status, and sensor break.

  • Alarm modes: Latching or non-latching.

  • Blocking: Energized or de-energized (failsafe) in alarm

  • Alarm delay: Off to 999.9 seconds

 

Communications:

  • Module types: RS-232, 2-wire RS-485, and 4-wire RS-485

  • Protocols: Modbus

 

Panel Sealing:

NEMA 4, or IP54 (EN60529)

 

Dimensions:

96mm (3.78In.)W x 48mm (1.89In)H

x150mm (4.01In.)D

 

EMC Compliance (CE Mark):

  • Emissions: EN50081-2

  • Immunity: EN50082-2

  • Safety: EN61010

 

Temperature:

  • Operating: 0 to 55°C (32 to 131°F)

  • Storage: -30 to 75°C (-22 to 167°F)

 

Humidity:

5 to 95%RH, non-condensing

 

Power:

Standard 100 to 240VAC, -15%,+10%,

optional 24V dc, -15%, +20%; 15 W max.

 

Agency Approvals:

  • cUL approved per standard UL508.

  • CE conformance per EMC directive 89/

  • 336/EEC, amended by 93/68/EEC and Low Voltage Directive 73/23/EEC, amended by 93/68/EEC.

 

Ordering Information

Specify:

1. Model Number:

  • V408 - ALGNVH (Green LED, 100-240VAC)

  • V408 - ALRDVH (Red LED, 100-240VAC),

  • V408 - ALGNVL (Green LED, 20-29VAC)

  • V408 - ALRDVL (Red LED, 20-29VAC),

2. Accessories: (see Accessories)

3. Optional Factory Configuration, specify C620 with the desired

 configuration information.

Accessories

The VisiPak model V408 is shipped with mounting brackets, 2.49 Ohm shunt

resistor and user manual. In addition, the following accessories are available:

  • SUB2K-D5 2nd Input

  • SUB2K-R4 Form C Relay

  • SUB2K-D6 DC Re-trans

  • SUB2K-TK Triple Contact Input

  • SUB2K-TL Triple Logic Input

  • SUB2K-TP Triple Logic Output

  • SUB2K-RR Dual Relay

  • SUB2K-LR Logic Relay

  • SUB2K-Y2 485 Comms

  • SUB2K-A2 232 Comms

  • SUB2K-F2 422 Comms

  • SUB2K-MS 24V, 20mA Exc.

  • SUB2K-G3 5V, Transducer Exc.

  • SUB2K-G5 10V Transducr Exc.

 

Get a Quote

» Indicates required fields

Request for Quote
Your Details
Company Details
*Leave State / Province Code  blank if not applicable*
Contact Details
Product Requirements

Get Support

Visit the Eurotherm Support site